Per-unit system

Normalises quantities to base values for easier power-system calculations.

In depth

Quantities are divided by base values: X_pu=actual/base. Transformer impedances are the same on both sides in pu, and three-phase systems simplify. Choose S_base and V_base, then Z_base=V²/S. Change base by Z_new=Z_old(S_new/S_old)(V_old/V_new)².

Key points

  • Avoids voltage-level conversion
  • Typical impedances 0.05–0.15 pu
  • Used in fault and load-flow studies
Example

A 10% reactance on 100 MVA is 0.1 pu.

Why it matters

The per-unit system makes power calculations easier, because quantities are normalised to base values and transformer ratios often disappear.

Where this is used

  • Analysing a transformer in a power flow study without tracking turns ratios.
  • Checking the impedance of a generator on a common base.
  • Comparing the ratings of different equipment in a system model.

Frequently asked questions

What is Per-unit system?

Normalises quantities to base values for easier power-system calculations.

Why is it important to understand per-unit system?

The per-unit system makes power calculations easier, because quantities are normalised to base values and transformer ratios often disappear.

What is a base value?

A chosen reference for voltage, power, current and impedance. Each per-unit quantity is the actual value divided by its base.

Why does the per-unit system help with transformers?

Voltage bases can be chosen so the transformer ratio becomes one, so many transformer models simplify.

How is Per-unit system used in practice?

Typical applications include analysing a transformer in a power flow study without tracking turns ratios, checking the impedance of a generator on a common base and comparing the ratings of different equipment in a system model.

What should I learn before Per-unit system?

Study "Transmission lines" first (topic 67 of 106 in Electrical Engineering). It covers the groundwork this topic builds on.

What are the key points of Per-unit system?

Avoids voltage-level conversion. Typical impedances 0.05–0.15 pu. Used in fault and load-flow studies.

Can you give an example of Per-unit system?

A 10% reactance on 100 MVA is 0.1 pu.

What comes after Per-unit system?

The next topic is "Line parameters", which builds directly on this one.

How difficult is Per-unit system?

It is classed as Intermediate in Electrical Engineering (topic 68 of 106). It is an intermediate topic. Work through the beginner topics in Electrical Engineering first.

Learning path

Want to practise? Open the interactive course for quick checks, quizzes, simulations and progress tracking.

Related topics